Earthing an Off-Grid Solar System — Notes, Numbers and Measurements

RSS

Another one off the usual IT-services path: notes on earthing (grounding) a small off-grid solar system — a 12 V, 2.2 kW all-in-one inverter with roof-mounted panels and an existing set of earth rods. It covers what the wiring rules require, the neutral–earth bond that cheap inverters often leave out, where the fuses or breakers go on an unearthed battery, what an earth resistance of 28 Ω actually means, and how to measure electrodes and soil properly.

6,167 words — approximately 26 minutes reading time

I don’t expect this article to be read by anyone else but me, and it serves as my “open note”, just like the arsenic article beforehand. Nonetheless, contributions are welcome.

How to read the sources

Numbers in square brackets, like [1] , link to the References section at the end. The reference list is grouped by topic, so the numbers there are not in sequence.

Standards (IEC, IEEE) are the authority but are paywalled, so they are linked to their official listing or preview pages. Manufacturer application notes and engineering articles explain the standards. Forum threads are field experience from installers and users and should be read as such, not as authority. Some sources are commercial (SPD manufacturers’ guides, e.g. [15] [39] ) or secondary study and summary sites of unclear authorship ([12] [22] [36] [40] ); they are cited where their content matches the standards and better sources, but they are the weakest references here. The battery fusing sources from Blue Sea Systems and MarineHowTo ([42] [43] ) are written for boats, where the battery negative is grounded, unlike in this system. Statements marked (engineering estimate) are calculations or common practice without a single specific source.

ItemDetails
AC output230 V / 50 Hz, single-phase
PanelsRoof-mounted
InverterEASUN POWER 2.2 kW hybrid, 12 V battery, 80 A MPPT, PV input up to 450 V, pure sine
Existing earth electrodes7 × 2 m rods (≥ 3 m apart) + 1 × 6 m rod (~8 m from the nearest), all interconnected
Measured earth resistance~28 Ω (fall-of-potential method, measured in a very dry summer)

Mostly yes. For permanent installations (house, cabin, workshop), wiring codes require an earthing system:

Exceptions: small portable or vehicle systems (vans, boats, camping kits) often run floating, with metal parts bonded to the chassis instead. Fully floating systems (IT systems) have their own special requirements [7] . Follow the manufacturer’s instructions.

  1. Protective earth (PE) and bonding. All exposed metal (panel frames, rails, inverter chassis, enclosures) is connected so a fault has a defined path and breakers or RCDs trip.
  2. AC reference point. The inverter creates its own mains supply. Bonding neutral to earth at one point makes the system behave like normal mains (TN-S) and lets RCDs work [7] .
  3. Lightning and surge protection. It gives surge protectors (SPDs) somewhere to divert spikes. IEC 62305 recommends a single integrated earth termination system shared by lightning protection, power and telecoms [27] .

Many low-cost all-in-one inverters of the Axpert / MPP Solar / WKS type do not bond N to PE when running from battery. Users of these units commonly measure roughly 100–110 V between neutral and earth in battery mode, and 0 V in bypass (grid) mode [5] . Others see the same pattern with a socket tester: earth is missing only when running from battery [9] . Without a bond, downstream RCDs are ineffective [7] . Some newer versions do bond internally with a relay [4] [6] , so measure rather than assume. (That the EASUN unit shares this platform is an inference from its specifications; the test below settles it.)

Test: disconnect the AC input, run from battery, and measure N → PE at the output. Users recommend measuring in both line mode and battery mode [5] .

ReadingMeaningAction
~0 VAlready bonded internallyDo nothing
~100 V (about half the output voltage)Floating neutralAdd a bond (see below)

Fix:

Where the bond goes: make it between the inverter output and the first RCD, never on the load side of an RCD. A bond downstream of an RCD lets neutral current return through the PE conductor, bypassing the RCD, which causes nuisance tripping and defeats its protection (engineering principle; not from a cited source).

Only one N–PE bond in the whole system [6] .

At 12 V and 2.2 kW, battery current is well over 200 A: 2200 W ÷ ~11 V ≈ 200 A, plus inverter losses (at ~90% efficiency about 220 A), and more during motor start-up surges. Use thick cables (often ≥ 50 mm² depending on length) and properly rated protection right at the battery (engineering estimate / common practice). A single fuse at the battery positive is the convention for negative-grounded systems; an unearthed battery like this one is better served by double-pole protection. Section 4 covers where the fuses or breakers go on an unearthed battery.

  1. N–PE voltage in battery mode: ~0 V [5]
  2. Earth electrode resistance test (fall-of-potential) [20]
  3. RCD test button, plus ideally a proper RCD trip-time test against the maximum operating times [35]

The battery here is unearthed (floating): neither pole is connected to earth, in line with section 3.4. With well over 200 A flowing at 12 V (section 3.6), where the fuses or breakers go on the battery cables matters. The system first had a separate fuse on each battery cable, and on overload the negative fuse always blew first. This section explains why, and why both fuses were replaced with a double-pole DC breaker.

TermMeaning
Positive (+)Battery + terminal, normally the red cable
Negative (−)Battery − terminal, normally the black cable

Current flows in a loop. During discharge, electrons leave the negative terminal, go through the external circuit and return to the positive; conventional current is defined the opposite way, and both describe the same thing. The same current flows through both cables at the same time, so a fuse on either cable sees exactly the same current.

“Hot” means voltage relative to a reference (usually earth), not electron direction. The hot conductor is the one not connected to the reference (engineering principle):

The negative fuse did not blow first because more current flowed through it — it is the same current. Overload tripping is thermal, and fuses have manufacturing tolerances, so the one that runs hotter goes first: a loose or corroded holder, a warmer location, or a slightly different fuse type (engineering principle).

The negative cable runs hotter too. During charging, the black cable between the inverter and the DC breaker gets noticeably warmer than the red cable next to it. Heat in a cable is P=I2RP = I^2 R. With the same current in both, the hotter cable has more resistance somewhere, cools less well, or picks up heat from something it is connected to (engineering principle). Likely causes, roughly in order:

  1. The inverter’s internal current measurement. Many all-in-one inverters measure battery current with a shunt resistor or a PCB trace in the negative path, just behind the terminal. It gets warm under heavy current, and the copper conducts that heat into the black cable. The red cable has no such heat source. This is a common design, but not confirmed for this inverter (engineering estimate).
  2. The termination at the inverter. A loose screw, a lug too large for the stud, or a poor crimp adds contact resistance. At 200 A, 1 mΩ of contact resistance gives 40 W in one spot.
  3. The termination at the breaker, or the negative pole’s internal contact.
  4. The cable itself: a smaller cross-section, copper-clad aluminium (CCA) instead of copper, or a longer run than the red cable.

Alternate paths (section 4.4) cannot explain this. A second path on the negative side would take current away from the black cable and make it cooler, not hotter.

Finding the cause (engineering principle):

Measuring safely under load (engineering principle). Measuring with current flowing is the point of this test, and it is safe in itself. In DC volts mode the meter has an input impedance of about 10 MΩ and draws only microamps, so the 200 A stays in the copper. The hazards come from the battery behind the cables, which can deliver thousands of amps into a short circuit:

On a 48 V system (engineering principle), the same test applies, but the risks change:

Common guidance is a single fuse on the positive cable, close to the battery:

This applies only partly to a floating system. The “positive shorts to the chassis” argument assumes a grounded negative. In a properly floating system, a positive cable touching earthed metal does nothing on its own. Unintended connections on the negative side can still create such a path, though (section 4.4).

Reasons for the positive fuse that do apply here:

The battery negative is often connected to the inverter by more than the main black cable:

If only the negative fuse opens while the system is loaded, the loop is not necessarily broken: the return current can take one of those thin paths instead. That wire was never meant to carry 200 A, so it melts, or the electronics it connects are damaged.

The positive is the safer side to open. Almost all incidental connections are on the negative side. The positive side normally has only the one fused cable, so opening it really breaks the loop.

Victron documents this. Quoting Wiring Unlimited (p. 35), breaking the negative while a data cable still connects devices “will cause a current in the negative signal of the data cable”, and “this current can damage the inverter/charger’s communication chip”. Victron’s example is paralleled inverters [47] .

If nothing else shares the battery negative, a blown negative fuse simply stops the system, the same as a blown positive fuse.

The “positive only” rule comes from systems with a grounded negative. For an unearthed battery, stricter practice protects and isolates both poles:

Two separate fuses are not the ideal answer. They blow independently, which is exactly what happened here: the negative opened alone, and that is the alternate-path situation from section 4.4.

The separate fuses were replaced with a 2-pole DC breaker:

Check on its label or datasheet (engineering principle where not cited):

  1. DC-rated at or above the battery voltage (e.g. “DC 125 V”), not only AC-rated. ABYC requires a DC voltage rating of not less than the nominal system voltage [42] .
  2. Non-polarized, or approved for current in both directions. Many DC breakers are polarized (+/− or an arrow on the terminals) and are only guaranteed to interrupt current in one direction. A battery breaker carries current both ways: discharge and charge.
  3. Breaking capacity above the battery’s short-circuit current. A 12 V bank, especially lithium, can deliver several thousand amps into a short. A breaker with too low a breaking capacity can arc over and weld shut; ABYC sets the required interrupt capacity by battery size, e.g. 1500–5000 A for a 12 V main breaker [42] . The usual fix is a class-T fuse at the battery positive ahead of the breaker: the fuse handles dead shorts, the breaker handles overloads and isolation. Fuses need an adequate interrupt rating too [43] .
  4. Current rating: about 220 A continuous plus inverter surges without nuisance tripping, while staying below the battery cables’ rating. At this current it will be a DC-rated 2-pole MCCB (moulded-case circuit breaker), not a small DIN-rail unit.

Alternatives:

Distance from the battery: as close as practical. Marine rules for unsheathed cable are within 7 in (175 mm) under ABYC [42] and within 200 mm under the European ISO rule [43] . Don’t put fuses, breakers or switches inside a battery compartment, because of corrosion and possible explosive gases [42] .


A safety switch that compares the current on live and neutral. If they differ (current leaking to earth, e.g. through a person), it trips: within 300 ms at its rated leakage current, and within 40 ms at five times that [35] . A 30 mA RCD trips at 30 mA of leakage, low enough to prevent a fatal shock.

Does nothing in normal operation. During a voltage spike (nearby lightning, switching) it briefly conducts and diverts the spike to earth. Long DC cables from the array act like antennas for surges from nearby strikes [39] .

All of these devices are DIN-rail modules.


The resistance is really that of the soil around the electrode. Rod surface area is a weak lever; length (depth) is a strong one.

Dwight’s formula for a single rod (published 1936) [17] :

R=ρ2πL(ln⁡4La−1) R = \frac{\rho}{2\pi L}\left(\ln\frac{4L}{a} - 1\right)

ρ\rho = soil resistivity (Ω·m), LL = rod length (m), aa = rod radius (m). Equivalent form with diameter dd: ln⁡8Ld−1\ln\frac{8L}{d} - 1. It assumes uniform soil [17] .

Worked examples at ρ = 100 Ω·m (engineering estimate, computed from the formula):

ElectrodeResistance
1.5 m rod, 16 mm diameter~60 Ω
1.5 m rod, 32 mm diameter (2× surface area)~52 Ω (−12%)
3 m rod, 16 mm diameter (2× surface area)~34 Ω (−44%)

A thicker rod is mainly useful for strength when driving, not for lower resistance.


Rough estimate using Dwight’s formula at average soil (100 Ω·m), 16 mm rods:

The measured 28 Ω is about 4× higher, which points to soil resistivity around 400 Ω·m or more, consistent with sand, gravel or stony ground [19] . This treats the soil as uniform. In reality the dry top layer is probably much worse than this average and the deeper soil better, which is exactly what a Wenner survey would reveal.

The measurement was taken in a very dry summer. Earth resistance changes with soil moisture, temperature and season [12] , and an electrode installed in moderate weather can become ineffective in a different season [11] .


Only worth it if there is (or will be) an external lightning protection system, or the site is very exposed. The 10 Ω figure is the IEC 62305-3 recommendation [26] [27] .

  1. On the same day, measure the 6 m rod alone (disconnected), then the seven 2 m rods alone.
  2. Illustrative example (engineering estimate, not real numbers): if, in dry conditions, the 6 m rod alone measured about 50–55 Ω and the seven 2 m rods together also about 50–55 Ω, the combination would come to roughly 28 Ω. (Two equal resistances in parallel give half the value, about 25–28 Ω, slightly more because the two groups still share some soil.) In uniform soil the seven short rods would measure lower than the 6 m rod (section 7), but dry topsoil hurts the short rods most, so in a drought the two can come out similar.
  3. Each extra 6 m rod of about 50 Ω adds roughly 0.016–0.02 S of conductance once some mutual coupling is allowed for. Getting from about 28 Ω (≈ 0.036 S) to 10 Ω (0.1 S) would then need roughly 0.064 S ÷ 0.016–0.02 S ≈ 3–4 more well-spaced 6 m rods; plan for 4, or 5 if coupling turns out worse. Your own measurements will give the real figure.

Defined in IEEE Std 81 [20] [28] .

Methods that don’t work here:

Defined by Frank Wenner in 1915 [24] ; standardized in ASTM G57 [40] and also described in IEEE Std 81 (not confirmed by the cited sources).

C1 ---- a ---- P1 ---- a ---- P2 ---- a ---- C2
Result as spacing growsMeaningBest option
ρ fallsDeeper soil conducts betterLonger or deeper rods
ρ stays high or risesDeep layers no better (sand, gravel, rock)Horizontal ring or strip, backfill
ρ low at small spacing, rising with depthGood soil near the surfaceShallow horizontal electrodes [26]

Tips:


Key requirement: 4 terminals and explicit 4-pole / Wenner / soil resistivity support [24] .

ModelNotes
Sonel MRU-11Budget; 3-pole, 4-wire and Wenner [30]
Kyoritsu KEW 4106Mid-range; calculates ρ from the stake spacing; four test frequencies; warns about high stake resistance and interference [29]
Megger DET4TC2Professional standard; 4-pole [24] . DET4TCR2 kit with clamps listed at ~$4,400 in the US [31]

Renting is a good option for a one-off survey; for example, the Megger DET4 is offered for hire [32] .

Avoid (no Wenner capability):

Look for: “4-wire / 4-pole” and “soil resistivity / Wenner” in the listing. Example: ETCR3000B, which does 2-, 3- and 4-wire earth resistance plus Wenner soil resistivity, and lists IEC 61557-5 [33] .

Before ordering, check:

Expectations: budget testers are fine for comparisons and ballpark values (engineering judgement). Sanity check: re-measure the existing system with the 3-pole method in similar weather and see whether you get close to 28 Ω.


  1. Measure N → PE in battery mode and add the bond if the neutral floats [5] .
  2. Confirm RCDs and SPDs (AC and PV-rated DC) are fitted, and that PV± and battery negative are not earthed [2] [15] .
  3. Check the battery breaker against the four points in section 4.6. If its breaking capacity is too low for the battery, add a class-T fuse at the battery positive.
  4. Check the national rules and the battery manufacturer’s manual for double-pole requirements [46] [48] . Keep communication cables in mind: they are the likely alternate paths if the negative is ever disconnected under load [47] .
  5. Find the source of the extra heat in the black cable between the inverter and the breaker: locate the hottest point during steady charging, then measure the millivolt drops on both cables (section 4.2).
  6. Get a 4-pole tester (or rent one).
  7. Re-check the 28 Ω reading with the current stake much farther out, plotting a curve of readings rather than relying on a single 62% point, since the 62% rule doesn’t apply directly to a multi-rod system [41] . The 52/62/72% check [22] is a quick first test.
  8. Measure the 6 m rod alone and the 2 m rods alone.
  9. Run a Wenner survey at 1–16 m spacings [23] .
  10. Re-measure in a wet season and, if the ground freezes, in a hard frost, using the same stake positions.
  11. Decide on extra electrodes only if a lightning protection system makes < 10 Ω necessary [26] .